Advanced
ramp and soak
•
Large
memory storage ....16 patterns/ 16 segments
• Autotuning
learning function
• Easy
programming with unique touch key
• Compact
size 96 x 96 mm
• Audible
verification of key operation
• Setting
lock function for security operation mode
• Mode
indicators RESET RUN FIX MAN SET enable easy
monitoring
• Program
pattern card simplifies program pattern checking
• 3 year
warranty
Programmable
Temperature Controllers Specifications
INPUT
Thermocouple. . . . Type J,K,T,E,B,R,S,N. (selectable)
RTD. . . . . . . . .PT 100 ohm(DIN or JIS)
Linear. . . . . . . -10-60mV Configurable input other voltage or current.
Display. . . . . . .in temperature or engineering units
OUTPUTS. . . . . . .Single output with 2 optional independent alarms
Heating and/or cooling outputs with 2 optional alarms
Relay. . . . . . . .SPST relay rated 3A, 240V maximum resistive load
Pulsed Voltage. . . 32VDC, 20mA maximum ohms
Current. . . . . . .4-20mA, 0-20mA maximum load 500 ohms
Voltage. . . . . . .0-10V minimum load 500K ohms
Alarms. . . . . . . 8 selectable modes each alarm
SPST relay(s) rated 2A, 240V maximum resistive load.
CONTROL FEATURES
Temp Range. . . . . Selectable Set Point: -1999-3182F/-1128-1750C
Alarm Set Point. . .Full Range Adjustable
Control Modes. . . .Controls can be configured as On/Off Proportional(P)
Proportional with manual reset
Proportional/Integral(PI) Proportional Derivative(PD)
Proportional/Integral/Derivative(PID)
Heating and Cooling Proportional Band:O-100% of span
Integral(Reset). . .0-3600 seconds
Derivative(Rate). . 0-1000 seconds
Anti-Reset Wind-up. Inhibits integral action outside of proportional band.
Cooling. . . . . . .Adjustable deadband from-10 to + 10% of cooling
proportional band
Manual Mode. . . . .Configurable as open loop control should sensor
no longer function
Cycle Time. . . . . 0-120 seconds
Sensor Break Protection. Configurable status of control and alarms
Control Action. . . Selectable-Direct action for cooling Reverse
action for heating
INDICATION
Display. . . . . . .4 digit red 5/8" LED Process Value Display.
Green 1.2" LED Set Value display
Selectable decimal placement for normal or high resolution display
Example. . . . . . .0000, 000.0, 00.00 or 0.000
F/C. . . . . . . . .Selectable with 2 LED indicators
Sample Rate. . . . .250 milliseconds
Data Retention. :. .l0years(EEPROM)
Control Stability. .+ - 0.15% of full scale
Accuracy. . . . . . + -0.25% of range: + ·-1 c or 0.5C
in high resolution
Cold Junction Compensation. .0.1 % ambient
External Resistance. . . . . 100 ohms maximum
Common Mode Rejection. . . . 120dB
Normal Mode Rejection. . . . 60dB
Input Impedance. . . . . . . 10M ohms
Operating Temperature. . . . 14-122F-10-50C
Humidity. . . . . . . . . . .0-90% RH(non-condensing)
Insulation. . . . . . . . . .20M ohm minimum (5OOVDC)
Breakdown. . . . . . . . . . 2OOVAC,5O/60Hz 1 minute
Vibration. . . . . . . . . . 10-55Hz amplitude 1 mm
Shock. . . . . . . . . . . . 200m/c(20g)