PID Temperature Controllers |
PID Temperature Controllers features dual displays &
selectable inputs. These PID Temperature Controllers are
easy to operate and the out can be ordered for a relay
contact, a voltage pulse, or a 4 to 20 mAmp output.
PID Temperature Controllers also excepts various inputs
from f thermocouples, RTD, DC voltage and DC current.
In addition these controllers can have 2 independent alarm
contacts that are programmable to be deviation, process,
or set value alarms.
The Heater break alarms utilize an external current transformer
that monitors the heater current and activates an alarm
should the current fall below a threshold value that has
been set by the operator. The loop break monitors and
protects the entire temperature control system.
The loop break alarm will detect Heater Breaks, Thermocouple
or RTD failure, short circuits, or the failure of an operating
device such as a mechanical relay, Mercury Relay or SSR.
PID Temperature Controllers Features:
•
Standard inputs thermocouple, RTD
• Heat/Cool action
• Relay, Triac, DC voltage pulse or current
output
• Heater break alarm for monitoring multiple
parallel heaters
• Loop break alarm for heater breaks/shorted
sensors or relays
PID
Temperature Controllers Specifications
Input
Thermocouple. . . . . . . . .K,J,R,S,B,T,L,N,E,PLII W5Re/W26Re.
RTD. . . . . . . . . . . . . (PIIOO,JPll OO) -199.9-649.0C -199.9-999 OF
DC voltage. . . . . . . . . .(0-5V,1-5V) 0.0-100%(fixed)
DC current. . . . . . . . . .(0-20mA, 4-20mA) 0.0-100%(fixed)
Control Output
Relay. . . . . . . . . . . . 25OVAC, 3A Form A or Form C contact
Voltage pulse. . . . . . . . 0/l2VDC, load resistance more than 600 Ohms
Current. . . . . . . . . . . 4-20mA DC load resistance less tham 600 Ohms
HBA Alarm
Input. . . . . . . . . . . . Output signal from CT
Range. . . . . . . . . . . . 0-30A or 0-100A
Accuracy. . . . . . . . . . .+/-0.5% or 2A whichever is larger
Relay output. . . . . . . . .25OVAC,1 A contact
Heating load draw:. . . . . .30 or 100 amps must be specified
LBA Alarm
Setting range 0.1-200.0 minutes.
Relay output 25OVAC,1 A contact
Control Action
a) PID action with autotuning
b) Heat/cool PID action with autotuning (not available on REX-C100)
Heating proportional band(P). 1-100% of input range.
Cooling proportional band. . .1-1000% of heating proportional band
Integral(1). . . . . . . . . .1-3600 seconds
Derivative(D). . . . . . . . .1-3600 seconds
ARW. . . . . . . . . . . . . .1-100% of proportional band
Heating cycle. . . . . . . . .1-100 seconds
Cooling cycle. . . . . . . . .1-100 seconds
Sampling Rate 0.5 seconds
Setting Accuracy Thermocouple input.+/-(0.5% of SV + 1 digit)
RTD input. . . . . . . . . . . +/-(0.5% of SV + 1 digit) 0.8C(1.6F)
External Dimensions
REX-C100. . . . . . . . . . . .48 x 48 x 100mm
REX-C400. . . . . . . . . . . .96 x 48 x 100mm
REX-C410. . . . . . . . . . . .48 x 96 x 100mm
REX-C700. . . . . . . . . . . .96 x 96 x 100mm
Supply Voltage 90-264VAC (50/6OHZ)